SPECIFICATIONS
Model: VT-3150-LX![]()
Notes
1. Derate heater output by 25% for 208/3/60 operation.
2. Consult factory for 50 HZ operation.
3. Unit weight crated for shipment.
STANDARD FEATURES
UNIT CONSTRUCTION:
• All stainless sheet metal cabinetry
• Upright design
• Easy access lift-off panel
• Twin tank design
• Hinged electrical panel
• Portable, on casters
CIRCULATING PUMP
• Centrifugal type
• Custom cast pump casing for
increased flow
• Bronze impeller
• Energy efficient pump motor
• Stainless steel motor shaft
• Overload relay protection
• Pump seal flush
HEATING
• Custom cast heater cylinder
• Dual voltage heater
• Flanged, bolt-in mount
• Mercury contactor
COOLING
• Custom cast cooling cylinder
• Modulating valve
• 0 to 100% aperture range
• Microprocessor controlled
• Integral to cooling tank
• Field serviceable
ELECTRICAL
• Fused transformer
• 10' power cord,
factory installed
LIMITS
• Water supply pressure switch
• Pressure relief valve
• High temperature limit
• Fused control circuit
WARRANTIES:
• 1 year on parts and labor
OPTIONS
• Closed circuit unitINSTRUMENT
• TEMPERATURE DISPLAYS:
Bright 9-segment 3 digit displays window that are easy to
read at distance. The upper window shows To Process temperature. The lower window shows Setpoint temperature.
• CONTROL RANGE:
30° - 250°F (0° - 120°C) control range.
• OPERATORS: The On/Off switch activates the unit. Setpoint temperature and other operating parameters are selected by the two soft key Arrow buttons. Unit Vent is activated by the Vent key.
• INDICATORS: Operating status is indicated by the Power, Pump, Heat and Cool lights.
• DIAGNOSTICS: Unit diagnostics is indicated by the Safety and Alarm lights. See manual for troubleshooting details.
• COMMUNICATIONS: Network communications is provided via the RS-422 port.
• WARRANTY: 2 year free replacement.
• SERVICE: After initial warranty period has expired, a standard $135 fee is charged for same day repair service if needed.